Connecting plant equipment to the cloud with outbound-only links

The reader questionHow do we send plant data to a cloud application without opening inbound paths into the OT network?

A tiny worker sending a capsule up a clear pneumatic tube that runs from a wall station out through the roof.

Put one small gateway inside the plant that reads machines locally and opens encrypted connections outward to a short list of named cloud endpoints. The plant firewall allows only those outbound flows, and no rule lets anything on the internet start a connection into the plant. If an outside party ever needs to reach in, for vendor support for example, that goes through a separate brokered path in a DMZ, never through the data path. This is the pattern set out in the January 2026 secure connectivity principles from the UK’s NCSC and its partners, and it matches the edge-gateway pattern in NIST’s September 2026 draft of SP 800-82 Rev. 4.

This article gives that design at small-plant scale: where the gateway sits, the firewall rules, the protocols on each leg, how the Purdue model and ISA/IEC 62443 zones still help, what outbound-only does not fix, and the questions to put to any cloud vendor. It covers data leaving the plant. People coming in, such as integrators and software vendors who need remote sessions, are covered in the companion article on vendor remote access to plant systems.

A disclosure first. OpenGXT builds, hosts and maintains cloud software for manufacturers and distribution centers, and its gateways connect outbound only, so we have an interest in this answer. The design works the same with any vendor, and the questions near the end are ones to ask us too.

What outbound-only means, and what it does not

Outbound-only means every connection that crosses the plant boundary is opened from inside the OT network, and nothing on the outside is listening for a way in. It does not mean any outbound traffic is allowed, and it does not make a plant safe on its own.

The NCSC puts the rule plainly in Principle 2 of its secure connectivity principles: “All connections with the OT environment should be initiated as outbound connections from within the OT environment.” The same paragraph explains why: it “helps avoid exposing inbound ports on the OT network perimeter or between internal zones.” An exposed port is something a scanner can find. A gateway that only dials out leaves nothing on the plant side to find.

Three details matter in practice:

  • Who opens the connection. In TCP, the side that sends the first packet initiates the session. A stateful firewall then lets the replies back in without a separate rule, which the NCSC describes as permitting return traffic for an authorized request. So data can still flow both ways inside a session the gateway opened.
  • Where it may go. NIST SP 800-82 Rev. 3 notes that the control of outbound traffic from the control network varies widely in practice, and that allowing outbound connections from lower levels “could represent a significant risk if unmanaged.” Its advice: “Organizations should consider making outbound rules as stringent as inbound rules” (NIST SP 800-82 Rev. 3, section 5.2.3.1). Outbound-only therefore means outbound to named destinations only.
  • What can come back. Because replies ride the same session, the design must decide what the hosted side may send down it. For a monitoring application the answer should be acknowledgments and configuration for the gateway, never writes to a controller.

The NIST draft of Rev. 4 lists the failure mode this guards against. Its appendix of OT vulnerabilities (Appendix C.2.2, Table 16) warns that “unnecessary outbound connections to external domains initiated by cloud platform agents or services may not be accounted for in existing firewall rules or network monitoring configurations, creating uncontrolled pathways outside the OT environment.” Outbound is the safer direction. It is not automatically a controlled one.

Outbound-only, unidirectional gateways and data diodes

A data diode is hardware that lets data travel in one direction only, so no reply can ever come back. Rev. 3 describes it as “an alternative to firewalls” that “permits authorized communication in only one direction.” An outbound-only firewall rule is weaker than that: it controls who starts the session, not which way the bytes flow once it is open.

The NCSC places both on one scale. Its Principle 5 says “Where possible, establish outbound only uni-directional connectivity,” at its simplest with uni-directional protocols such as UDP and network policy, and adds that high-threat or high-risk environments may consider “further hardware-based security controls.” CISA’s Performance Goal 3.I says the same for OT: “When applicable, physically segment OT enclaves (e.g., data diodes).”

For most small plants sending monitoring data, a firewall-enforced outbound session is the practical starting point. A diode changes the protocol design, because MQTT and HTTPS run over TCP and TCP expects replies. Consider one when a line carries safety-critical or high-consequence processes, or when your insurer or a customer asks for hardware-enforced separation.

What the 2025 and 2026 guidance says about OT to cloud connectivity

Five public sources now point the same way: open connections from inside, broker anything that must come in, separate the plant from the business network, and document every cloud link as its own path with its own rules. None of them is a certification scheme, and following them does not make a plant compliant with anything.

Source Date What it adds to this design
NCSC, Secure connectivity principles for OT, produced with ASD’s ACSC, the Canadian Centre for Cyber Security, CISA, the FBI, Germany’s BSI, NCSC-NL and NCSC-NZ Published January 14, 2026 Eight principles. Outbound initiation and brokered access through a DMZ (Principle 2), secure protocols such as OPC UA over TLS and MQTT over TLS for OT to IT data exchange (Principle 4), logging (Principle 7) and an isolation plan (Principle 8)
NIST SP 800-82 Rev. 3, Guide to OT Security September 2023 Segment by Purdue levels, ISA-95 levels or the three-tier IIoT model; add a DMZ as an enforcement boundary; make outbound rules as strict as inbound rules; consider unidirectional gateways
NIST SP 800-82 Rev. 4, initial public draft Published September 21, 2026; comments due November 30, 2026 New section 2.4.6 on cloud and IIoT convergence: telemetry-to-cloud, edge gateway and remote access patterns; shared responsibility; “cloud conduits” to document
CISA, FBI, EPA and DOE, Primary Mitigations to Reduce Cyber Threats to OT May 6, 2025 “Remove OT connections to the public internet”; segment IT and OT with a demilitarized zone; practice operating manually
CISA, Cybersecurity Performance Goals 2.0 Report revised December 11, 2025 Goal 3.S: segment networks, “including cloud-based platforms,” and only permit required communications; Goal 2.E: keep network topology documented and review it yearly

Two cautions about dates. Rev. 4 is a draft, so Rev. 3 remains NIST’s final guide until the new revision is published; as of November 2026 the comment period was still open. The NCSC documents are UK guidance, but the US agencies that co-authored them make them a fair reference for a US plant. The NIST Cybersecurity Framework 2.0, released on February 26, 2024, sits underneath both NIST documents, and the Rev. 4 draft is restructured around its six functions.

A reference design for a small plant

The design has five parts: devices stay on the plant floor network, one edge gateway reads them, one firewall rule lets the gateway reach named endpoints, an optional DMZ holds anything shared, and people who need to reach in use a separate brokered path. Every part is something a plant with one IT generalist and one controls engineer can build and check.

The NIST draft describes the gateway’s job precisely. In its edge gateway pattern, “OT devices communicate with an industrial gateway or edge platform that normalizes protocols, filters data, enforces policy, and forwards selected data to cloud, vendor, or enterprise systems.” In the companion telemetry-to-cloud pattern, “Control functions typically remain local.” Both sentences are from section 2.4.6 of the Rev. 4 draft.

Outside the plant Internet Boundary Between Levels 3 and 4 Levels 2 and 3 Levels 0 and 1 Hosted software MQTT broker on 8883, HTTPS on 443 TLS session opened by the gateway Plant firewall Allows the gateway to named endpoints only No inbound rule Optional DMZ: relay broker or replica, and a brokered access path for people Plant floor network Edge gateway reads only, buffers read requests Filler PLC OPC UA Torque monitor Modbus TCP Air flow meter Modbus RTU Red mark: inbound attempts stop at the firewall
Reference design for a small plant: one gateway reads devices on the plant floor network and opens the only connection across the boundary. The DMZ layer is optional. Level labels are approximate Purdue model positions. Device names come from the fictional Line 2 example. Sources: NCSC, Secure connectivity principles for OT, Principle 2 (January 14, 2026); NIST SP 800-82 Rev. 3, section 5.2.3.1; NIST SP 800-82 Rev. 4 initial public draft, section 2.4.6. Checked November 2026.

The five parts, one by one

  1. Devices stay put. PLCs, CNC controls, meters and sensors keep their addresses on the plant floor network. None of them gets a default route to the internet, and none needs one.
  2. One gateway reads them. The gateway polls or subscribes over OPC UA, Modbus TCP, Modbus RTU or MTConnect, with read-only accounts where the device supports accounts. It buffers data while the internet link is down and forwards it when the link returns, which is covered in store and forward at the edge.
  3. One firewall rule carries the data. The gateway, and only the gateway, may open connections to a few named endpoints on stated ports. The next section writes that rule set out.
  4. An optional DMZ. A DMZ is a separate network segment between the plant and everything outside it. It is optional at small scale and becomes the better choice as soon as more than one outside system needs plant data.
  5. A separate path for people. Remote sessions for integrators and vendors never ride the data connection. They get their own brokered, on-demand path, described in the vendor remote access article.

Single boundary or DMZ relay

A plant with no DMZ today can start with a single boundary: the gateway sits on the plant floor network, and the plant firewall allows its outbound flows. Industrial protocols never cross the firewall, because the gateway translates them to an encrypted protocol first. The NIST draft accepts a narrow version of this for one case it discusses: where staging in a DMZ is not available, an update client “is restricted to a tightly scoped outbound rule that permits only the specific vendor endpoint, documented as a risk acceptance” (section 5.2.1). Write the same risk acceptance for the gateway.

A DMZ relay puts a broker or data replica in the DMZ. The gateway publishes to it, and the relay publishes onward to the cloud. The NCSC’s worked example of OT data export uses this “push-only architecture”: “No listening ports are open on the OT side of the DMZ. All data must be pushed from the OT networks upward through the architecture.” The Rev. 4 draft explains why the second firewall helps: without that separation, “a single set of firewall rules must accommodate both trust levels and is, therefore, necessarily broader than either requires.”

Choose the DMZ relay when the plant already has one, when an ERP, a historian and a cloud application all want the same data, or when IT policy forbids plant-floor hosts from reaching the internet at all. Choose the single boundary when there is one consumer, one gateway and no DMZ to build on, and plan the move to a relay before the second consumer arrives.

Example (fictional). At a fictional beverage bottler, the Line 2 gateway sits in an existing enclosure next to the Line 2 control panel, on the plant floor network. It reads the filler PLC over OPC UA with a read-only account created by the controls engineer, the torque monitor and the electricity meter over Modbus TCP, and the compressed-air flow meter over Modbus RTU. Its only path out is one connection through the plant firewall to the hosted software, using MQTT with Sparkplug B over TLS. No inbound rule was added. The plant has no DMZ, so the IT/OT lead wrote a one-page risk acceptance for the single boundary and a note to revisit it when a second system asks for the data. The full walkthrough is on the example line page.

Where the gateway’s own management traffic goes

The gateway itself needs configuration changes, software updates and health checks, and that traffic deserves the same scrutiny as the data. There are two common patterns, and the vendor should say in writing which one it uses.

In the first, the hosted side sends configuration down the session the gateway opened. That keeps the firewall rule set short, but it makes the return-traffic question concrete: configuration may change the gateway’s own mapping, never a controller, and every change should land in the change log with an approval. In the second, administration happens only through the plant’s brokered remote access path, with a person on each end. The Rev. 4 draft describes the controls that path should carry: privileged access mediated by an access manager with “least-privilege entitlements, time-bounded session authorization, and session recording with live termination capability” (Table 8).

Either pattern can work. What does not work is a third, undocumented channel, such as a remote desktop agent on the gateway that nobody listed.

What the plant firewall allows

The firewall allows a short, written list of flows: the gateway may reach a few named endpoints on stated ports, everything else is denied and logged, and there is no inbound rule at all. If the list does not fit on one page, the design has more paths than it needs.

Write the rule set in this order:

  1. List each flow the gateway needs. Usually data publishing, name resolution, time, and software updates for the gateway itself. Ask the vendor for anything else, in writing.
  2. Name every destination. Use fully qualified domain names where the firewall can enforce them, or the address ranges the vendor publishes. Ask the vendor how it will tell you before an endpoint changes.
  3. Fix the ports. IANA registers TCP 8883 as “secure-mqtt” and TCP 1883 for MQTT without TLS, and the MQTT 5.0 standard recommends that servers offering TLS use 8883. HTTPS uses TCP 443. Allow 8883, not 1883.
  4. Point name and time lookups inward. Let the gateway use the plant’s own DNS and NTP servers rather than public ones, so those flows never cross the boundary.
  5. Time-box what is occasional. Enable the update flow during an agreed maintenance window and disable it afterward.
  6. Deny and log the rest. Default deny in both directions, with denied packets logged, so an unexpected attempt shows up as evidence rather than silence.
#SourceDestinationPort and protocolDirectionPurpose
1Gateway 10.20.2.50broker.example.netTCP 8883, MQTT over TLSOutboundPublish line data
2Gateway 10.20.2.50Plant DNS 10.20.0.10UDP and TCP 53Inside the plantResolve the broker name
3Gateway 10.20.2.50Plant NTP 10.20.0.10UDP 123Inside the plantSynchronized timestamps
4Gateway 10.20.2.50updates.example.netTCP 443, HTTPSOutbound, maintenance window onlyGateway software updates
5Gateway 10.20.2.50Filler PLC 10.20.2.11TCP 4840, OPC UAInside the plantRead-only account
6Any outside addressAny plant addressAnyInboundNo rule: denied and logged
7Any plant addressAny outside addressAnyOutboundDenied and logged
Example rule set for one gateway. Fictional example: addresses and host names are placeholders (example.net is a domain reserved for use in examples, RFC 2606). Port registrations: IANA service name and port number registry (opcua-tcp 4840, secure-mqtt 8883, domain 53, ntp 123, https 443), checked November 2026.

Two further questions belong in the review. The first is whether to inspect the encrypted traffic. The NCSC notes that deep packet inspection of a TLS channel “requires interception and decryption,” so the inspecting device must be fully trusted (Principle 6). A plant that skips inspection can still keep the destination list tight and watch traffic volumes instead.

The second is where the rule set lives. Put it in the connection plan, on the data-flow and network diagram, and in the change log. CISA’s Performance Goal 2.E asks organizations to keep network topology documentation accurate, review it every year and update it whenever the topology changes.

Which protocols fit each leg

Keep industrial protocols such as Modbus and OPC UA on the plant side, and cross the boundary only with an encrypted, authenticated protocol that the gateway initiates: MQTT over TLS, HTTPS, or OPC UA with security enabled. The NCSC says the same in Principle 4: industrial control protocols “should be restricted to isolated OT network segments,” and external data exchange should use protocols “such as OPC UA over TLS, MQTT over TLS, HTTPS.”

Leg Typical protocol Who opens the connection What to check
Device to gateway OPC UA (TCP 4840 by default) Gateway, as the OPC UA client Security policy and certificates agreed with the plant; read-only user on the server
Device to gateway Modbus TCP, Modbus RTU Gateway, as the polling client Keep it on the plant floor segment; scaling and units checked per register
Device to gateway MTConnect Gateway, requesting from the agent Agent address stays inside the plant
Gateway to cloud MQTT over TLS on TCP 8883 Gateway, as the MQTT client TLS version, broker certificate, client credentials or client certificate
Gateway to cloud HTTPS on TCP 443 Gateway Same TLS checks; used for file uploads and APIs
Plant OPC UA server to an outside client OPC UA with Reverse Connect The plant-side server The outside client must validate that the connection comes from the expected server

The MQTT standard settles who dials whom: an MQTT client is a program or device that “opens the Network Connection to the Server” (OASIS MQTT 5.0). A gateway publishing to a hosted broker is therefore outbound by construction. The Eclipse Foundation describes Sparkplug, the convention many gateways use on top of MQTT, as one that “requires no open port for edge of network devices” (Sparkplug). Whether Sparkplug or plain MQTT fits your data is a separate decision, covered in Sparkplug B or plain MQTT.

OPC UA usually works the other way, with a client connecting to a server. When an outside OPC UA client must collect from a plant server without an inbound rule, the specification’s Reverse Connect option lets the server open the connection instead. OPC 10000-2, section 6.14 notes the extra duty this puts on the client: it “needs to validate that the connection is from an appropriate Server and not a denial of service attack.”

Three settings apply on every leg that crosses the boundary:

  • TLS version. NIST SP 800-82 Rev. 3 says that “Only TLS 1.2 or above should be considered” (section 6.2.10).
  • Certificates that are planned, not discovered. CISA’s Secure by Demand guidance asks for certificates that “fail loudly (e.g., when a certificate expires)” while critical processes continue. Put every expiry date in the support calendar.
  • Data you can validate. The NCSC recommends simple data formats and schemas checked at trust boundaries, on a “known good” model. A gateway that publishes a fixed set of named signals is easier to validate than one that forwards whatever a device sends.

Yes, as a map of what may talk to what, not as a rule that data must climb one level at a time. NIST still uses Purdue levels in Rev. 3 and in the Rev. 4 draft, and it adds the IIoT tier model and documented cloud conduits beside them.

The Purdue model sorts plant systems into levels. ISA describes the ISA-95 levels, which rely on the Purdue model, as Level 0 for the physical production processes, Level 1 for sensing and manipulating them, Level 2 for monitoring and supervising control, Level 3 for manufacturing operations management and Level 4 for business planning and logistics. Rev. 3 tells organizations they “may also consider using an industry-recognized model to organize their OT network segmentation,” naming the Purdue model, ISA-95 levels, the three-tier IIoT system architecture, or a combination of them (section 5.2.3.1). Its firewall advice is to permit connections only between adjacent levels and to prevent Level 4 devices from talking directly to Levels 2, 1 or 0.

A gateway that sends Level 1 data straight to a cloud service skips levels by design. That is acceptable when the skip is a single, documented path with its own rules, and dangerous when it is an untracked side channel. The Rev. 4 draft names this case. Organizations “should pay particular attention to cloud conduits,” which are connections to cloud services “that may bypass traditional network boundaries and introduce exposure that is not immediately visible in standard network diagrams. These connections should be explicitly identified, documented, and assessed as part of the baseline process” (section 4.1.2).

“Conduit” is a term from ISA/IEC 62443, the series that, in ISA’s words, defines “requirements and processes for implementing and maintaining electronically secure industrial automation and control systems” (ISA). The NCSC summarizes the zones and conduits model as grouping assets with similar security needs into zones and “defining controlled communication paths (‘conduits’) between them” (Principle 1). The risk assessment method behind it is ISA-62443-3-2, security risk assessment for system design.

Zone in a small plant Typical contents Conduits that leave it
Devices and controllers PLCs, CNC controls, drives, meters, I/O modules To the gateway, read requests only
Plant floor network HMIs, the edge gateway, engineering workstation Gateway to the cloud or to the DMZ relay; nothing else outward
DMZ, if present Relay broker or replica, remote access broker Relay to the cloud; brokered sessions inward for people
Business network Office PCs, ERP, email No direct path to the plant floor
Hosted software Broker, application, storage Back to the gateway only inside sessions the gateway opened

The practical step is to draw your plant this way once, give each conduit a written rule, and keep the drawing current. The OT security checklist has the zone and firewall items to tick before the first gateway goes in.

What outbound-only does not solve

Outbound-only closes the inbound door. It does not protect a compromised gateway, stop a tunnel someone opens from inside, decide what data leaves, or tell you how to cut the link in a hurry.

A compromised gateway is already inside

The gateway sits on the plant network and reads controllers, so it is a target in its own right. The NCSC warns that “OT gateway devices, serial gateways, and network switches aggregate multiple assets, making them high-value targets,” and that an insecure gateway “can also offer attackers a persistent point of presence” (Principle 6). The answers are read-only accounts on the devices it reads, patching on a schedule, logging, and a rule that monitoring systems never gain control capability. The NCSC puts that last rule directly: monitoring, analytics and business systems “should be designed to observe and analyse, not command or alter operations.”

Outbound tunnels can carry people inward

Remote access tools usually dial out to a cloud relay, then let someone outside drive a machine inside. CISA’s Guide to Securing Remote Access Software (June 6, 2023) lists among the risks that such software “could allow actors to bypass firewall rules.” An outbound-only firewall does not stop this, because the session looks outbound. Inventory every remote access tool, allow only approved ones, and route vendor sessions through the brokered path in the vendor access article.

Side doors never cross your firewall

The Rev. 4 draft is direct about this: “Cellular modems and vendor-managed connections can bypass enterprise and OT network security controls. Organizations should inventory and approve these connections, restrict what they can reach, monitor their use where possible, and prevent them from creating unmanaged paths into OT networks” (section 2.4.6). Walk the panels. A cellular router in a machine cabinet is a cloud link nobody drew.

The data question is a contract question

Outbound-only says nothing about what the vendor keeps. The draft asks that “Terms of use, contracts, and service agreements should define data ownership, access rights, storage location, third-party sharing, retention, deletion, and security protections.” Those terms are the subject of data ownership and exit terms.

The draft says organizations should “determine which OT functions can tolerate loss of cloud, vendor, or communications services,” and that safety, protection and time-critical control “should generally remain capable of local operation.” A monitoring gateway outside the control path meets this by design: if it fails, machines keep running and the data gap is recorded.

An isolation plan you have tried

The NCSC’s Principle 8 asks for an isolation plan that is “regularly tested.” Its data export example layers it: isolate one customer from a feed, isolate one feed, isolate all outward feeds, or isolate the OT side from the DMZ. At small-plant scale, the minimum is one documented step that cuts the gateway’s uplink without stopping a machine, and a record of the last time someone did it.

Questions to ask any cloud vendor before you connect

Ask for the exact endpoints and ports, who opens each connection, what can travel back toward the plant, how certificates and credentials are handled, what is logged and who can see it, and how you cut the link without stopping a machine. Get the answers in writing before the gateway is powered on.

The NIST draft frames why the answers matter. Organizations “should define responsibility for identity and access management, patching, configuration, monitoring, logging, incident response, backup, vulnerability handling, and recovery,” which “may be shared among OT, IT, cloud providers, SaaS providers,” integrators and equipment vendors. A written answer to each question below turns that shared responsibility into named tasks.

Question Why it matters Where the expectation comes from
Which destinations, ports and protocols does your gateway use, and how will you tell us before one changes? You cannot write a tight outbound rule without the list NIST SP 800-82 Rev. 3, outbound rules as strict as inbound
Does any feature need an inbound rule or a listening port on our side? The answer should be no NCSC Principle 2
What can your hosted side send down the connection, and can any of it write to a controller? Return traffic rides the gateway’s session NCSC Principle 6; Secure by Demand, secure controls
Which TLS versions do you accept, and what happens when a certificate expires? Expired certificates stop data; weak versions expose it NIST SP 800-82 Rev. 3, section 6.2.10; Secure by Demand, secure communications
Where are the credentials for our controllers stored, and who can read them? Gateway credentials open your devices Secure by Demand, strong authentication; CPG 2.0, goal 3.C
What does the gateway log, what does the hosted software log, how long are logs kept, and can we get them? Service logs live outside your plant NIST SP 800-82 Rev. 4 draft, section 4.3.1.1.2
How are gateway updates delivered, tested and approved? Updates are changes to an OT asset Secure by Demand, upgrade and patch tooling; CPG 2.0, goal 3.N
What happens to production if your service or our internet link is down? Control must stay local NIST SP 800-82 Rev. 4 draft, section 2.4.6
Will you give us a data-flow and network diagram and a list of the hardware and software you install? Your inventory must include the gateway CISA asset inventory guidance; CPG 2.0, goal 2.E
How do we isolate the link in an incident, and what do you need from us to restore it? Isolation should be planned, not improvised NCSC Principle 8

CISA’s Secure by Demand guidance was published on January 13, 2025 with the NSA, FBI, EPA, TSA and international partners to help OT owners and operators buy digital products. Its twelve elements are aimed at OT products, “particularly industrial automation and control system products,” but most apply to a data gateway too. One element, ownership, asks for products that “enable operator autonomy while minimizing dependency on the vendor.”

Ask OpenGXT the same questions. Our written answers, including where we hold no certification, are on the security page, and how hosted data is kept and exported is on cloud hosting.

Prove the design on the day you connect, then prove it again whenever the network changes. The proof is simple: nothing on the plant side answers from outside, the firewall log shows only the expected flows, and pulling the uplink stops no machine.

On the day of the first connection

  1. Approve the rule set in writing. The IT/OT lead signs the one-page list before the change, and the change log records who made it.
  2. Add the gateway to the asset inventory. CISA’s asset inventory guidance (August 13, 2025) defines an inventory as “an organized, regularly updated list of an organization’s systems, hardware, and software.” The gateway, its firmware version and its owner belong on it.
  3. Connect during a planned stop. The gateway reads only, but the first connection still touches controllers, so schedule it when a surprise costs nothing.
  4. Check from the outside. Scan the plant’s public addresses and confirm nothing new answers. The NCSC recommends external attack surface management so that accidental exposure is found “before attackers do.”
  5. Read the firewall log. Confirm the gateway’s flows appear as expected and that denied attempts are logged.
  6. Pull the uplink. Disconnect the gateway’s path out, confirm every machine keeps running, reconnect, and confirm the buffered data arrives without a gap.
  7. Send the logs somewhere central. CISA’s Performance Goal 3.Q asks that firewall and VPN logs be stored centrally, readable and changeable only by authorized users, and that security staff be notified “when a critical log function is disabled.”
  8. File the evidence. Put the results in the connection plan and the per-signal test record.

Example (fictional). During a planned stop on the fictional bottler’s Line 2, the IT/OT lead disabled the gateway’s outbound rule. The filler and capper kept running, the gateway buffered, and when the rule was re-enabled the buffered data arrived with no gap in the shift timeline. The external scan showed no new open ports. The test went into the pilot review as one of its acceptance measures.

After go-live

  • Review on change and once a year. Any new machine, gateway, vendor or firewall replacement triggers a review of the rule set. CISA’s Performance Goal 2.E sets the annual minimum for network documentation.
  • Watch for new side doors. New equipment can arrive with its own remote support router. Each one goes on the inventory, through the brokered path, or out of the panel.
  • Track certificates and endpoints. Expiry dates and vendor endpoint changes go into the support calendar, not someone’s memory.
  • Keep the isolation step current. Re-run the uplink pull after major network changes.

The connection work itself, including how each machine is read, is described under machine connectivity.

A one-page plan for your next network meeting

Bring five things to the meeting where the first gateway is approved. With them, IT, controls and operations can approve the link in one sitting and check it later against the same page.

  • A zone drawing of the plant with the gateway’s single conduit marked.
  • The outbound rule set, one page, with every destination named.
  • The vendor’s written answers to the ten questions above.
  • The commissioning steps, with a named person for each.
  • The isolation step: who disables the uplink, where, and how the plant knows it worked.

Then run the OT security checklist against your plant before any supplier connects, ours included. If you are planning a first line and want the connection plan written with you, you can plan a pilot line with us.