Data volume estimator for plant signals
How many values your machines will send, how much storage they need for the years you keep them, and what to measure before you trust the answer.
For: IT and OT leads, controls engineers and data engineers

Calculator
Before choosing where plant data lives and how long it is kept, it helps to know how much of it there will be. The answer depends on a handful of choices: how many signals you collect, how often you read them, how many readings you keep, and how well the storage compresses them. This estimator multiplies those choices out to values per day, storage per year and storage for the full retention period.
How the estimate works
These are plain multiplications, shown in the order the estimator applies them:
| Result | Calculation |
|---|---|
| Values stored per day | Tags × (86,400 seconds ÷ sample interval) × share kept |
| Uncompressed size per day | Values per day × bytes per value |
| Stored size per day | Uncompressed size ÷ compression ratio |
| Stored size per year | Stored size per day × 365 |
| Stored size for retention | Stored size per year × years kept |
| Values per second at the server | Values per day ÷ 86,400 |
The share kept is what remains after report by exception or deadband filtering: a value is sent only when it changes, or changes by more than a set amount. Sizes use decimal units, so 1 MB is 1,000,000 bytes and 1 GB is 1,000,000,000 bytes.
Example (fictional). A fictional plant collects 400 tags, sampled every second. After deadband filtering, 20% of samples are kept. Each stored value takes 16 bytes (timestamp, value and quality), storage compresses 4 to 1, and data is kept for three years.
- Values stored per day: 400 × 86,400 × 20% = 6,912,000
- Uncompressed size per day: 6,912,000 × 16 bytes = 110.6 MB
- Stored size per day: 110.6 MB ÷ 4 = 27.6 MB
- Stored size per year: 10.1 GB
- Stored size for three years: 30.3 GB
- Values per second arriving at the server: 6,912,000 ÷ 86,400 = 80.0
Without deadband filtering every sample would be kept, and every figure above would be five times larger.
Collecting good inputs
- Tags. Count them from your signal inventory, not from the controller’s full tag list. Most controllers hold far more tags than any report needs.
- Sample interval by group. Signals are not all read at the same rate. Machine states and fault codes are usually sent on change, counts every few seconds, temperatures and pressures every few seconds to a minute. Run the estimator once per group and add the results.
- Share kept. This is the input that moves the answer most and the one people guess. Measure it on a real line for a week before sizing storage. Event-heavy tags, such as fault words during an upset, change it.
- Bytes per value. The 16-byte default assumes a timestamp, a numeric value and a quality flag. Strings, such as batch or product codes, take more; check how your database stores them.
- Compression ratio. It depends on the database or historian and on how smooth the data is. Measure it on a week of real data rather than taking it from a brochure.
Reading the result
For most plant signal lists, the storage figure is modest. The more useful numbers are often elsewhere:
- Values per second. 80.0 is an average. Shift starts, changeovers and upsets come in bursts, so size the ingest path for several times the average.
- Network. The uncompressed 110.6 MB a day is about 1,280 bytes a second on average before protocol and encryption overhead, which matters on a plant with a thin internet connection.
- Store and forward. The gateway buffers data while the connection is down and sends it when the connection returns. One day of the example’s data is 110.6 MB before compression, which tells you how much local storage the gateway needs for each day of outage you want to cover.
- Copies. Backups, replicas and exports each add to the stored total. Agree how many copies are kept, and for how long, when the retention period is set.
Common mistakes
- Sizing at the poll rate. It overstates storage by the inverse of the kept share, five times in the example.
- Setting deadbands too wide to save space. Short events disappear, and a stop that lasted 40 seconds never reaches the shift report.
- Mixing binary and decimal units. Storage providers and operating systems do not always count a gigabyte the same way.
- Treating waveforms as tags. High-frequency vibration or power quality data is a different scale of problem and needs its own estimate.
Where this fits
Cloud hosting by OpenGXT covers the historian and data pipeline, backups, retention and exports, and the retention period is written down with you rather than assumed. Signal rates and deadbands are set per signal during machine connectivity work, and a consistent topic structure, which the topic namespace builder helps you draft, makes the data easier to query later. Whatever the volume, it stays exportable in open formats under our open data commitment.